booster heaters
Booster Heater Gas
 
Gas water heater
HOME
Products 
     
     


FireMax200™ Modular Water Heater    (Download PDF version)
Model: FM200N™ or FM200L™




Model Number BtuH per burner Natural or Propane Gas Connection Water Supply Electrical Connection Gas Pressure Regulators Shipping Weight
FM200™ 199,990 3/4" NPT 1" NPT 120V 1ph 6.2 amps One each Supplied 418 lbs

Natural Gas Pressure WC @ Inlet LP Gas Pressure WC @ Inlet Manifold Pressure WC Water Pressure (Flow) Re-circulating Loop
Min Max Min Max Nat LP Min Max
1"
7” 10.5” 10” 14” 3.5” 7.5” 40 psi 80 psi To Storage Tank

Clearance From Combustible Surface Vent Per Local Code
Side Top Rear Auxiliary Power Vent Required for extended flue lengths Call factory

6” L - 1” R

1” 6” **

Model/Storage Temp Rise 60°F 70°F 80°F 90°F 100°F 110°F
Output Temp 110°F 120°F 130°F 140°F 150°F 160°F
FireMax200™/120gal 1 hour 475 gal 420 gal 390 gal 360 gal 336 gal 320 gal
  2 hour 820 gal 740 gal 660 gal 600 gal 552 gal 520 gal
Firemax200™/240gal 1 hour 600 gal 540 gal 510 gal 480 gal 456 gal 440 gal
  2 hour 940 gal 860 gal 780 gal 720 gal 672 gal 640 gal

*Contact factory if booster will be supplying dishwasher fill valves or tank heat.
**1” from back of exhaust vent
Note: May be vented through the dishwasher canopy or pant-leg exhaust system per 1991 Uniform Mechanical Code Sec 916. & 917. Check with local authority

Water heater shall be a FireMax200™ gas water heater, Model FM200™ as manufactured by Vanguard Technology Inc., Eugene, OR 97402. Water Heater to be fired by a 199,990 Btu infrared power burner, using natural gas or liquid propane fuel, with a woven ceramic fabric element. Burner to be ignited by means of a hot surface igniter and a redundant intermittent pilot light. Heat exchanger to be of heavy duty finned copper tubing and carry a 5 year limited warranty. Standard equipment to include gas pressure regulating valve, internal bronze-stainless re-circulation pump, integrated solid state power control, temperature and pressure relief valve and LED temperature display. Water Heater frame, body panels, and flue collar shall be of all stainless steel construction. Unit shall stand on 6 inch adjustable stainless or composite NSF approved legs. Stainless steel front panel to be removable for access to all components without disconnecting water heater from its installed location. Water Heater to be rated at 88% operating efficiency, minimum. Water heater shall be connected and circulated to one or more hot water storage tanks and controlled by temperature sensors in tank(s).


29495 Airport Road, Eugene, OR 97402
Tel: 541-461-6020   Fax: 541-461-6023

 



FireMax200™
Features
Accessories
Specification
Manual/Catalog
Saving calculator
Warranty/Policies
 
 Contact us